M9F22220
Schneider Electric – BREAKER, CIRCUIT; TYPE: MCB, CURRENT: 20 A, VOLTAGE: 415 V, 72 V DC, ELECTRICAL POLE QUANTITY: 2P, INTERRUPT CAPACITY: 15 KA, APPLICATION: UPS SYSTEM (APPARENT POWER: 120 KVA, VOLTAGE: 240 V); ADDITIONAL INFORMATION: CURVE: C; MANUFACTURER: SCHNEIDER ELECTRIC, MANUFACTURER PART NO: 530-9575, MODEL NO: IC60H, EQUIPMENT MANUFACTURER: GUTOR ELECTRONIC LLC, EQUIPMENT MODEL NO: PEW 1120-220/240-EAN-D, PEW 1080-220/240-EAN-D 530-9575
SPECIFICATION
Range | Multi 9 |
---|---|
Product name | Multi 9 C60 |
Product or component type | Miniature circuit-breaker |
Device short name | C60SP |
Device application | Distribution |
Poles description | 2P |
Number of protected poles | 2 |
[In] rated current | 20 A at 25 °C conforming to EN/IEC 60947-2 |
Network type | DC AC |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | 14 kA AIR at 240 V AC conforming to UL 1077 14 kA AIR at 240 V AC conforming to CSA C22.2 No 235 10 kA AIR at 480Y/277 V AC conforming to UL 1077 10 kA AIR at 125 V DC conforming to UL 1077 10 kA AIR at 480Y/277 V AC conforming to CSA C22.2 No 235 10 kA AIR at 125 V DC conforming to CSA C22.2 No 235 6 kA Icu at 440 V AC conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC conforming to EN/IEC 60947-2 20 kA Icu at 240 V AC conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC conforming to GB 14048.2 10 kA Icu at 415 V AC conforming to GB 14048.2 20 kA Icu at 240 V AC conforming to GB 14048.2 |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Standards | EN/IEC 60947-2 GB 14048.2 UL 1077 CSA C22.2 No 235 |
Product certifications | IEC CCC UR CSA |