M9F22232


Schneider Electric – BREAKER, CIRCUIT; TYPE: MCB, CURRENT: 32 A, VOLTAGE: 220-440 V, ELECTRICAL POLE QUANTITY: 2P, INTERRUPT CAPACITY: 10-20 KA, APPLICATION: UPS SYSTEM (VOLTAGE: 110 V); ADDITIONAL INFORMATION: CHARACTERISTICS: CURVE C; MANUFACTURER: SCHNEIDER ELECTRIC, MANUFACTURER PART NO: 530-9543,  EQUIPMENT MANUFACTURER: GUTOR ELECTRONIC LLC, EQUIPMENT MODEL NO: SDC 110-125-R, SDC 110-50-R, 530-9543

Compare

M9F22232

Schneider Electric – BREAKER, CIRCUIT; TYPE: MCB, CURRENT: 32 A, VOLTAGE: 220-440 V, ELECTRICAL POLE QUANTITY: 2P, INTERRUPT CAPACITY: 10-20 KA, APPLICATION: UPS SYSTEM (VOLTAGE: 110 V); ADDITIONAL INFORMATION: CHARACTERISTICS: CURVE C; MANUFACTURER: SCHNEIDER ELECTRIC, MANUFACTURER PART NO: 530-9543,  EQUIPMENT MANUFACTURER: GUTOR ELECTRONIC LLC, EQUIPMENT MODEL NO: SDC 110-125-R, SDC 110-50-R, 530-9543

SPECIFICATION

Range Multi 9
Product name Multi 9 C60
Product or component type Miniature circuit-breaker
Device short name C60SP
Device application Distribution
Poles description 2P
Number of protected poles 2
[In] rated current 32 A at 25 °C conforming to EN/IEC 60947-2
Network type AC
DC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 14 kA AIR at 240 V AC conforming to UL 1077
14 kA AIR at 240 V AC conforming to CSA C22.2 No 235
10 kA AIR at 480Y/277 V AC conforming to UL 1077
10 kA AIR at 125 V DC conforming to UL 1077
10 kA AIR at 480Y/277 V AC conforming to CSA C22.2 No 235
10 kA AIR at 125 V DC conforming to CSA C22.2 No 235
6 kA Icu at 440 V AC conforming to EN/IEC 60947-2
10 kA Icu at 415 V AC conforming to EN/IEC 60947-2
20 kA Icu at 240 V AC conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC conforming to GB 14048.2
10 kA Icu at 415 V AC conforming to GB 14048.2
20 kA Icu at 240 V AC conforming to GB 14048.2
Suitability for isolation Yes conforming to EN/IEC 60947-2
Standards EN/IEC 60947-2
GB 14048.2
UL 1077
CSA C22.2 No 235
Product certifications IEC
CCC
UR
CSA

 

Category: